Description:High Limit strap-on mounting Manual Reset Aquastat Controller with 100F to 240F operating temperature
Includes:
- Bracket for strap-on mounting, stop factory-set at 240F (116C), and heat-conductive compound.
Application:
- High Limit strap-on mounting on well mount.
- Insulation Depth (in.): 1 1/2 in.
- Insulation Depth (mm): 38 mm
- Bulb Size (in.): 3/8 in. x 2 7/8 in. copper
Bulb Size (mm): 10 mm x 73 mm copper - Switching Action: SPST, contacts break on temperature rise.
- Operating Temperature Range (F): 100F to 240F
- Operating Temperature Range (C): 38C to 116C
- Electrical Ratings (millivolt): 0.25 A @ 0.25 to 12 Vdc
- Electrical Ratings (AFL): 8A @ 120 Vac. 1.3A @ 240 Vac
- Electrical Ratings (ALR): 48A @ 120 Vac. 30.6A @ 240 Vac
- Differential Temperature (F): Manual Reset
- Differential Temperature (C): Manual Reset
- Maximum Ambient Temperature (F): 150F
- Maximum Ambient Temperature (C): 66C
- Case Dimensions (in.): 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep
- Case Dimensions (mm): 143 mm high x 51 mm wide x 54 mm deep
- Mounting: Horizontal or Vertical Mounting
- Approvals, Underwriters Laboratories Inc: UL Component Recognized
- Approvals, Canadian Standards Association: Certified: File No. LR95329-1